Opened 19 months ago
Last modified 13 months ago
#69 accepted requirement
Alarmausgang
| Reported by: | (none) | Owned by: | Erik Welander |
|---|---|---|---|
| Priority: | major | Component: | Ein- und Ausgänge |
| Keywords: | Cc: | ||
| Data type: | Deadline: | ||
| Depending on: | 153,181,182 | Implements: | |
| Memaddress: | Observerlist: | ||
| Parent: | #134 | Answer: | |
| Type: | system | Revieweraccept: | |
| Reviewerlist: | welander | Reviewerreject: | |
| Priority: | normal | Visibility: | |
| Writable: | Class: | quality | |
| Priority: | must have |
Description (last modified by )
Das Gerät muss mindestens eine von anderen Digitalausgängen unabhängige zweipoligen Alarmausgang aufweisen, die nach Kundenwunsch durch die Kabelverschraubung nach Außen geführt werden kann.
Der Alarmausgang soll zur Ausgabe von dem Alarmstatus verwendet werden. Die Polarität soll auswählbar sein, d.h. "normally closed" oder "normally open".
Change History (11)
comment:1 by , 19 months ago
| Component: | Gesamtsystem → Ein- und Ausgänge |
|---|---|
| Reporter: | removed |
comment:2 by , 17 months ago
| Description: | modified (diff) |
|---|---|
| Parent: | #10 → #134 |
| Summary: | Warn- und Alarmausgänge → Alarmausgänge |
comment:3 by , 17 months ago
| Description: | modified (diff) |
|---|
comment:4 by , 17 months ago
| Summary: | Alarmausgänge → Alarmausgang |
|---|
comment:5 by , 16 months ago
comment:6 by , 16 months ago
| Description: | modified (diff) |
|---|
Nach Diskussion mit Sebastian am 04.10.2024: "normally open" wird ab und zu nachgefragt
comment:7 by , 15 months ago
| Reviewerlist: | welander → welander,hantzsch |
|---|---|
| Status: | new → submitted |
comment:8 by , 15 months ago
| Reviewerlist: | welander,hantzsch → welander |
|---|
comment:9 by , 15 months ago
| Status: | submitted → accepted |
|---|
comment:10 by , 14 months ago
| Depending on: | → 192 |
|---|
comment:11 by , 13 months ago
| Depending on: | 192 → 153,181,182 |
|---|
Note:
See TracTickets
for help on using tickets.
![(please configure the [header_logo] section in trac.ini)](/rsm600_req.bak/chrome/site/rmglogo.png)
Der Alarmausgang wird normalerweise als "normaly closed" ausgeführt (im Fehlerfall und bei ausgeschaltetem Gerät geschlossen). Ist der Polaritätswechsel notwendig?